The zinc oxide arrester is the most advanced over-voltage protector in the world. Because its core component is zinc oxide resistor, compared with the conventional silicon carbide arrester, this prescription of the product improves greatly the volt-ampere characteristics of the resistor disc and increased the flowing ability at over-voltage so as to bring a radical change for the characteristics of the arresters.
◆Keystone
The zinc oxide arrester is the most advanced over-voltage protector in the world.Due to make the resistor disc of core component mainly adopt zine oxide arrester. Compared with the conventional silicon carbide arrester,this presciption of the product improves greatly the volt-Ampere characterisics of the resistor disc and increased through-current capability at over-voltage so as to bring a radical changes for the characteristics of the arresters.
Under the circumstance of normal operating voltage, the current through the arrester is just on microampere degree.When suffered from over-voltage,the arresters excellent nonlinear characteristics will make the current through the arrester increase to several thousand amperse, while the arrester will be under the circulating state and release over-voltage energy so as to protecting the power thansmission equipments against the damage caused by the over-voltage.
◆Condition of Use
The ambient air temperatures is no higher than+40℃, no lower than-40℃.
The altitude above sea level does not exceed 1000-2000m (the altiplanoarea should be indicated when order ).
AC system frequency 50Hz or 60Hz.
lndustrial frequency voltage brought to bear on arrester for a long time does not exceed arresters sustained operation
voltage.
Maximum wind speed does not exceed 35m/s.
The earthquake intensity does not exceed 7 degrees.
The filthy area should be given clear indication.
◆Application & Characteristics
The zinc oxide arrester applies to protect the electrical equipment in AC power system against the damage resulted from atmospheris over-Voltage and operational over-voltage
◆Technical performance
The technical performance of the prodect is in conformit to GB 110322000, IEC60099-4&IEEE.C62.11 standard technic requirements.
◆Type instruction
Gapless arrester electrical character
Type |
Rated voltage (Kv) |
MCOV (Kv) |
Sparkover voltage (Kv) |
Lighting Impulse residual voltage |
200us square wave impulse current withstand |
4/10us high current impulse |
|
Power frequency |
1.2/50uss Lighting Impulse |
||||||
Y5c-3 |
3 |
2.55 |
5.0 |
7.8 |
9 |
100 |
65 |
Y5c-6 |
6 |
5.1 |
10.0 |
15.5 |
18 |
100 |
65 |
Y5c-9 |
9 |
7.65 |
16.5 |
24.5 |
27 |
100 |
65 |
Y5C-12 |
12 |
10.2 |
21.0 |
32.6 |
36 |
100 |
65 |
Y5C-15 |
15 |
12.7 |
25.0 |
38.8 |
45 |
100 |
65 |
Y5C-18 |
18 |
15.3 |
31.0 |
48.1 |
54 |
100 |
65 |
Y5C-21 |
21 |
17.0 |
34.0 |
52-7 |
63 |
100 |
65 |
Y5C-24 |
24 |
19.2 |
39.0 |
60.5 |
72 |
100 |
65 |
Y5C-27 |
27 |
21.9 |
45.0 |
69.8 |
81 |
100 |
65 |
Y5C-30 |
30 |
24.4 |
50.0 |
77.5 |
90 |
100 |
65 |
Y5c-33 |
33 |
26.8 |
55.0 |
85.3 |
99 |
100 |
65 |
Y5C-36 |
36 |
29 |
60.0 |
93.0 |
108 |
100 |
65 |
Y5C-42 |
42 |
34.1 |
70.0 |
108.5 |
126 |
100 |
65 |
Note: if it is porcelain,without"H"
Gapless arrester electrical character (line discharge class l)
Type |
Rated voltage (Kv) |
MCOV (Kv) |
Sparkover voltage (Kv) |
8/20us Lighting Impulse residual voltage |
200us square wave impulse current withstand |
4/10us high current impulse |
|
Power frequency |
1.2/50uss Lighting Impulse |
||||||
Y10C-3 |
3 |
2.55 |
5.0 |
7.8 |
9 |
1 |
100 |
Y10C-6 |
6 |
5.1 |
10.0 |
15.5 |
18 |
1 |
100 |
Y10C-9 |
9 |
7.65 |
16.5 |
24.5 |
27 |
1 |
100 |
Y10C-12 |
12 |
10.2 |
21.0 |
32.6 |
36 |
1 |
100 |
Y10C-15 |
15 |
12.7 |
25.0 |
38.8 |
45 |
1 |
100 |
Y10C-18 |
18 |
15.3 |
31.0 |
48.1 |
54 |
1 |
100 |
Y10C-21 |
21 |
17.0 |
34.0 |
52-7 |
63 |
1 |
100 |
Y10C-24 |
24 |
19.2 |
39.0 |
60.5 |
72 |
1 |
100 |
Y10C-27 |
27 |
21.9 |
45.0 |
69.8 |
81 |
1 |
100 |
Y10C-30 |
30 |
24.4 |
50.0 |
77.5 |
90 |
1 |
100 |
Y10C-33 |
33 |
26.8 |
55.0 |
85.3 |
99 |
1 |
100 |
Y10C-36 |
36 |
29 |
60.0 |
93.0 |
108 |
1 |
100 |
Y10C-42 |
42 |
34.1 |
70.0 |
108.5 |
126 |
1 |
100 |
The two functions of a fuse are overcurrent protection and isolation. The function of a fuse cu...
High voltage fuse links is composed of conductor material, insulating material and circuit brea...
The structural components of high-voltage fuses mainly include melt, fuse tube, contact conduct...
As we all know, fuses are the most commonly used protection devices in power systems. So how to...
How does a low-voltage fuse work? Decipher the working principle and function of the fuse!A fus...
How many kv are high voltage fuses widely used in?High-voltage fuses are widely used in 3-35kV ...
Shanghai Zhiguang Fuse Co., Ltd provides related answers to questions such as what are the fact...
Welcome to Shanghai Zhiguang Fuse Co., Ltd. We are a low-voltage fuse manufacturer in China. Ma...