It can be used in indoor system of 50Hz and rated voltage of 3.6KV, 7.2KV, 12KV, 24KV and 40.5KV. Used together with other switch facilities such as loading switches, vacuum contactors, it can protect electric transformers and other electric facilities against overloading or circuit break. It is also a necessary accessory for high-voltage switch.
Type |
Counterpart |
Rated voltage (KV) |
Rated current of the fuse (A) |
Rated current of the fuse link (A) |
XRNT-12 |
SDLAJ |
12 |
40 |
3.15、6.3、10、16.20、25、31.5、40 |
XRNT-12 |
SFLAJ |
12 |
100 |
50、63、71、80、100、(125) |
XRNT-12 |
SKLAJ |
12 |
125 |
125.160、200、250 |
XRNT-24 |
|
24 |
200 |
3.15、6.3、10、16、20、25、31.5、40、50、63、8o、100、125、160、200 |
XRNT-40.5 |
|
40.5 |
125 |
3.15、6.3、10、16、20、25、31.5、40、50、63、80、100、125 |
Basic parameters
The basic parameters of the fuser are shown in Table 1 and Table 2
Main technical data
(1) The fuse should be able to break any fault current between the minimum breaking current l3 and the maximum breaking current h. ls current is about 4 times the rated current
(2) The time-current characteristics are shown in Figure 1, and the part above the minimum breaking current l3 is the dotted line
Shape and installation dimensions
The appearance and installation dimensions of the fuse are shown in chat2, chat3, chat4
Table1
Type |
Rated voltage (A) |
Fuse rated current (A) |
Main parameters (mm) |
Rated maximum breaking current (kA) |
Dimensions |
|
length |
diameter |
|||||
BFY□-40.5KV/□A |
40.5 |
3.15、6.3、10、16、20、25、31.5、40、50 3.15、6.3、10、16、20、25、31.5、40、50 |
650 |
Φ76 |
31.5 |
Plug-in type see Figure 2 |
Bus type see Figure 3 |
||||||
XRNT□-40.5 KV/□A-31.5-1 |
3.15、6.3、10、16、20、25、31.5、40、50 |
See picture 4 |
◆Technique data
Type |
Rated voltage UN (KV) |
Rated current IN(A) |
Diameter×Length (mm) |
Rated breaking current [KA) |
XRNT1 |
3.6/7.2 |
6.3 |
Φ50X192 Standard size |
63 |
10 |
||||
16 |
||||
20 |
||||
25 |
||||
31.5 |
||||
40 |
||||
50 |
||||
63 |
Φ76X192 Standard size |
|||
80 |
||||
100 |
||||
125 |
||||
160 |
Φ88X192 Standard size |
|||
*200 |
50 |
|||
*250 |
||||
6.3 |
Φ51X292 Standard size |
63 |
||
10 |
||||
16 |
||||
20 |
||||
25 |
||||
31.5 |
||||
40 |
||||
50 |
||||
63 |
Φ76X292 Standard size |
|||
80 |
||||
100 |
||||
125 |
||||
160 |
Φ88X292 Standard size |
50 |
||
*200 |
||||
*250 |
||||
*315 |
||||
*355 |
||||
100 |
Φ76X442 |
63 |
||
125 |
||||
160 |
Φ88X442 |
|||
*200 |
50 |
|||
*250 |
||||
*315 |
||||
*355 |
||||
*400 |
||||
*500 |
Type |
Rated voltage UN (KV) |
Rated current IN(A) |
Diameter×Length (mm) |
Rated breaking current [KA) |
Foreign reference model |
XRNT1 |
6/12 |
6.3 |
Φ51X192 |
63 |
SDLAJ |
10 |
|||||
16 |
|||||
20 |
Φ76X192 |
||||
25 |
|||||
31.5 |
|||||
40 |
|||||
2 |
Φ51X292 Standard size |
||||
3.15 |
|||||
6.3 |
|||||
10 |
|||||
20 |
|||||
31.5 |
|||||
40 |
|||||
50 |
Φ63X292 Φ76X292 Standard size |
SFLAJ |
|||
63 |
|||||
80 |
|||||
100 |
|||||
125 |
SKLAJ |
||||
*160 |
Φ88X292 Standard size |
50 |
|
||
*200 |
|||||
6.3 |
Φ51X442 |
63 |
High-voltage current-limiting fuse for high-voltage center cabinet |
||
10 |
|||||
16 |
|||||
20 |
|||||
25 |
|||||
31.5 |
|||||
40 |
|||||
50 |
Φ76X442 Standard size |
||||
63 |
|||||
80 |
|||||
100 |
|||||
125 |
|||||
160 |
Φ88X442 Standard size |
||||
*200 |
50 |
||||
*250 |
(*) Please pay attention to the use of derating, please refer to the reasonable selection of fuse.
Type |
Rated voltage UN( KV) |
Rated current IN(A) |
Diameter×length (mm) |
Rated breaking current (KA) |
XRNT1 |
20/24 |
6.3 |
Φ53X442 Standard size |
|
10 |
||||
16 |
63 |
|||
20 |
||||
25 |
||||
31.5 |
||||
40 |
||||
50 |
Φ63X442 Standard size |
|||
63 |
||||
80 |
||||
100 |
||||
125 |
Φ88X442 Standard size |
40 |
||
160 |
||||
200 |
||||
36/40.5 |
6.3 |
Φ51X442 |
31.5 |
|
10 |
||||
16 |
||||
6.3 |
Φ51X537 Standard size |
40 |
||
10 |
||||
16 |
||||
20 |
||||
25 |
Φ76X537 Standard size |
|||
31.5 |
||||
40 |
||||
50 |
Φ88X537 Standard size |
|||
63 |
||||
80 |
||||
160 |
(*) Please pay attention to the use of derating, please refer to the reasonable selection of fuse.
Transformer capacity KVA |
Transformer primary voltage 7.2kV |
|
Fuse rated voltage KV |
Fuse rated current A |
|
100 |
7.2 |
20 |
125 |
20 |
|
160 |
25 |
|
200 |
31.5 |
|
250 |
40 |
|
300/315 |
50 |
|
400 |
71 |
|
500 |
80 |
|
630 |
100 |
|
750/800 |
140 |
|
1000 |
160 |
|
1250 |
200 |
Transformer capacity KVA |
Transformer primary voltage 12kV |
|
Fuse rated voltage KV |
Fuse rated current A |
|
100 |
12 |
16 |
125 |
16 |
|
160 |
16 |
|
200 |
20 |
|
250 |
25 |
|
300/315 |
31.5 |
|
400 |
40 |
|
500 |
50 |
|
630 |
63 |
|
750/800 |
80 |
|
1000 |
100 |
|
1250 |
125 |
|
1500/1600 |
160 |
|
2000 |
200 |
Transformer capacity KVA |
Transformer primary voltage 24kV |
|
Fuse rated voltage KV |
Fuse rated current A |
|
100 |
24 |
6.3 |
125 |
6.3 |
|
160 |
10 |
|
200 |
10 |
|
250 |
16 |
|
300/315 |
16 |
|
400 |
20 |
|
500 |
25 |
|
630 |
31.5 |
|
750/800 |
40 |
|
1000 |
50 |
|
1250 |
63 |
|
15000/1600 |
80 |
|
2000 |
100 |
|
2500 |
125 |
|
3150 |
160 |
|
4000 |
200 |
Transformer capacity KVA |
Transformer primary voltage 12kV |
|
Fuse rated voltage KV |
Fuse rated current A |
|
50 |
35 |
2 |
100 |
3.15 |
|
125 |
5 |
|
160 |
5-6.3 |
|
200 |
6.3 |
|
250 |
8-10 |
|
315 |
10-12 |
|
400 |
12-16 |
|
500 |
16 |
|
630 |
20-25 |
|
800 |
25-31.5 |
|
1000 |
31.5-40 |
|
1250 |
40-50 |
|
1600 |
50 |
|
2000 |
63 |
Type |
Equivalent model |
Rated voltage (kV) |
Fuse rated current (A) |
Main parameters (mm) |
Rated maximum breaking current (kA) |
||
C |
ΦD |
||||||
XRNT□-3.6 |
ADF*□ |
3.6 |
6.3、10、16、20、25、31.5、40 |
254 |
Φ51 |
50 |
|
ADG*□ |
6.3、10、16、20、25、31.5、40、50、63、80、100 |
359 |
|||||
XRNT□-7.2 |
ADF*□ |
7.2 |
6.3、10、16、20、25、31.5、40、50、63 |
254 |
|||
BDG*□ |
6.3、10、16、20、25、31.5、40、50、63、80 |
359 |
|||||
AFF*□ |
80、100 |
254 |
Φ76 |
||||
BFG*□ |
100 |
359 |
|||||
BKG*□ |
125、140、160 |
||||||
XRNT□-12 |
BDG*□ |
12 |
6.3、10、16、20、22.4、25、31.5 、35.5、40、45、50 |
359 |
Φ51 |
||
XRNT□-12 |
BFG*□ |
12 |
56、63、71、80、90、100 |
359 |
Φ76 |
||
AKG*□ |
112、125 |
||||||
AKG*□ |
160、200 |
Φ88 |
Note: 1. The above are the rated parameters of a single tube. A fixed structure can be used to connect the fuse in parallel according to user needs to obtain a high rated current value;
2. "Represents different types of impactors.
Main technical data
(3) The fuse should be able to break any fault current between the minimum breaking current l3 and the rated maximum breaking current.
●The fuse below the rated current 125A does not include 125A l3 current is about 4 times the rated current.
●Rated current above 125A includes 125A l3 current is about 7 times the rated current.
(4) The time-current characteristic is shown in Figure 1, and the part above the minimum breaking current is the dotted line.
Shape and installation dimensions
The appearance and installation dimensions of the fuse are shown in Figure 2 to Figure 8.
Selection of fuse
The general selection of fuses for the primary side of the transformer is shown in Table 2
Table2
Transformer capacity KVA |
Transformer primary voltage 3.6KV |
|
Fuse rated voltage KV |
Fuse rated current A |
|
100 |
3.6 |
31.5 |
125 |
40 |
|
1160 |
50 |
|
200 |
63 |
|
250 |
80 |
|
300/315 |
90 |
Transformer capacity KVA |
Transformer primary voltage 3.6KV |
|
Fuse rated voltage KV |
Fuse rated current A |
|
100 |
7.2 |
20 |
125 |
20 |
|
160 |
25 |
|
200 |
31.5 |
|
250 |
40 |
|
300/315 |
50 |
|
400 |
71 |
|
500 |
80 |
|
630 |
100 |
|
750/800 |
140 |
|
1000 |
160 |
Transformer capacity KVA |
Transformer primary voltage 3.6KV |
|
Fuse rated voltage KV |
Fuse rated current A |
|
100 |
12 |
16 |
125 |
16 |
|
160 |
16 |
|
200 |
20 |
|
250 |
25 |
|
300/315 |
31.5 |
|
400 |
40 |
|
500 |
50 |
|
630 |
63 |
|
750/800 |
71 |
|
1000 |
90 |
|
1250 |
112 |
|
1500/1600 |
125 |
Contact the manufacturer for the selection of transformers in special cases and the selection of other power equipment.
The two functions of a fuse are overcurrent protection and isolation. The function of a fuse cu...
High voltage fuse links is composed of conductor material, insulating material and circuit brea...
The structural components of high-voltage fuses mainly include melt, fuse tube, contact conduct...
As we all know, fuses are the most commonly used protection devices in power systems. So how to...
How does a low-voltage fuse work? Decipher the working principle and function of the fuse!A fus...
How many kv are high voltage fuses widely used in?High-voltage fuses are widely used in 3-35kV ...
Shanghai Zhiguang Fuse Co., Ltd provides related answers to questions such as what are the fact...
Welcome to Shanghai Zhiguang Fuse Co., Ltd. We are a low-voltage fuse manufacturer in China. Ma...